Home ProductsLow Frequency UPS

Online Low Frequency UPS Generator 200KVA/160KW With Transformer

Good quality Single Phase Online UPS for sales
Good quality Single Phase Online UPS for sales
I'm Online Chat Now

Online Low Frequency UPS Generator 200KVA/160KW With Transformer

China Online Low Frequency UPS Generator 200KVA/160KW With Transformer supplier
Online Low Frequency UPS Generator 200KVA/160KW With Transformer supplier Online Low Frequency UPS Generator 200KVA/160KW With Transformer supplier

Large Image :  Online Low Frequency UPS Generator 200KVA/160KW With Transformer

Product Details:

Place of Origin: China
Brand Name: CPSY
Certification: CE.TLC
Model Number: GP33200K

Payment & Shipping Terms:

Minimum Order Quantity: 1units
Price: USD/pcs
Packaging Details: wooden box
Delivery Time: 25-35days
Payment Terms: T/T, Western Union
Supply Ability: 500pcs per month
Contact Now
Detailed Product Description
Type: Online Low Frequency Ups Capacity: 200KVA/160KW
Phase: Three Phase Online Ups Usage: Industrial Equipment, Boiler Room,etc
Maintenance Bypass Type: Without Interruption Maintenance Bypass Voltage: 3*400V(3PH+n)
Size: 1051×705×1646mm Net Weight(KGS): 840

Online low frequency UPS generator 200KVA three phase ups price online ups ups with transformer

 

Feature:
-Online double conversion
-DSP Technology guarantee high reliability
-True galvanic isolation transformer design
-Control designed to withstand all kinds of load
-Intelligent battery management to prolong battery lifecyclet
-Independent ventilation enhance durable operation under harsh environment
-Accept dual-mains input
-Adjustable battery numbers
-Parallel operation with up to 4units (option)
-Variety of communication options available
-Optional 7"touch LCD
-Reverse phase frequency operation and supports non-neutral input
-Built-in maintenance bypass switch
-Output power factor 0.8

 

Feature:

1) DSP Technology

2) Superior overload capability

3) Large LCD display and LED indicator

4) 50/60Hz source auto detection

5) Emergency Power Off (EPO)

6) Advanced battery charging management

7) N+X parallel redundancy

8) Fault detection and alarming

9) The efficiency of the machine is more than 93%, and reach 98% in ECO mode.

10) High security dual ac power input function

11) The frequency and phase sequence adaptive system

12) Powerful panel Settings function

13) Intelligent RS485+SNMP+AS400 communication port

 

 

 

Parameter:

 

Model GP3360K GP3380K GP33100K GP33120K GP33160K GP33200K
Capacity 60KVA/48KW 80KVA/72KW 100KVA/80KW 120KVA/96KW 160KVA/128KW 200KVA/160KW
INPUT
Norminal Voltage 3*380VAC/400VAC(3PH +N)
Acceptable voltage range 285VAC~475VAC
Frequency Range 50Hz/60Hz±10%
INVERTER
Norminal voltage 380V
Precision 380V±25%
Frequency 50Hz/60Hz
Waveform Pure Sine wave
Total Harmonic Distortion(THDv) ≤2% (linear load); ≤5% (non-linear load)
Phase Displacement 120°±1%(balanced load); 120°±2%(imbalances 50% of the load)
Dynamic Recovery Time 3 cycles at 90% of the static value
Admissible Overload 110% for 10min;150% for 60sec;>160% for 200ms
AdmissibleCrest Factor 3:01
Admissible Power factor 0.6~1(inductive or capacitive)
Imbalance output voltage@100% unbalanced load <1%
Current limit High overload, short circuit, RMS voltage limit, High Crest-factor Curren, Peak voltage limit
STATIC BYPASS
Type Solid state
Voltage 3*380VAC/400VAC(3PH +N)
Frequency 50Hz/60Hz
Activation Criterion Microprocessor control
Transfer time Zero
Admissible Overload 150% for 1hour;180% for 30sec;>200% for 200ms
Transfer to Bypass Immediate, for overload above160%
Retransfer Automatic after alarm clear
MAINTENANCE BYPASS
Type Without Interruption
Voltage 3*400V(3PH+n)
Frequency 50Hz/60Hz
Overall Efficiency Line mode 105%±5% ≤load,warning overload;
Battery Mode 105%±5% <load≤125%±5% Transfer to bypass and Alarming after 2 mins;
BATTERY & CHARGE
Battery type & Number 12VDC*32pcs(29~32pcs adjustable)
Normal Battery Voltage 384VDC(Based on 32pcs batteries)
Charging Method CC/CV
Charging Current Default 10A, Max.40A;5A@ full load
Charging Voltage 432VDC(Based on 32pcs batteries)
Safety requirements GB4943-2001/IEC62040-1 EMC/EMI, IEC 61000-4-5 Protection surge
Noise(1m) ≤55dB
PHYSICAL
Dimension,D×W×H (mm) 821×432×1159 975×554×1286 975×554×1326 1051×705×1646
Net Weight(KGS) 365 471 573 650 760 840

 

 

3/3 low frequency ups application:

 

small and medium sized data centers,Server,critical network devices, sensitive electronic equipment,small rooms, small precision electronic instrument

 

 